Metering system for truck and railcar loading
Model : ZCE 6-250
ZCE 6 horizontal metering unit is designed for truck and train tankers loading stations in a top bottom configuration
ZCE 6 space-saving configuration enables easy installation in smaller facilities and in compact pipeline network.
Sector of appliacation
- Tanker trucks and railcars loading applications
- Presparation of bio-fuels by means of line or batch blending
- Measurement of white product and bio-fuels
High reliability measuring system
Ready-made technology ZCE 6 horizontal measuring systems are completely assembled, wired and tested in the production facility in order to ensure a maximum reliability
Measurement stability and accuracy Measurement accuracy guranteed over a period of many years without any deviation in the calibrate curve
Modular design
Extensive line of accessories to create customized measurement applications
Key points
low intallation costs
Complete and ready-to-install measuring unit including strainer, air eliminator, PD meter, valve and register
Low maintenance costs
Simple and robust construction with minimal moving parts Interchargeble mechanical components
Space-saving installation
Compact metering unit for installation in smaller areas and in vertical pipeline networks
A safe and easy-to-use-technology
Automatic gas elimination system to start loading operation with empty pipe. Filtering system with automatic clogging detection (option)
Communication
Direct communication with supervisory system with the electronic register version.
Technical data-Horizontal metering system
Measuring system : ZCE 6-250
Maximum flow rate m3.h-L/mn-USGPM : 250-4166-1100
Application : Tanker truck and rail car loading application, product transfer
Measured parameter : Actual volume, temperature-corrected volume, mass, flow rate, temperature (only for electronic register version option for mechanical register version)
Measured liquids ; Petrol, premium fuels, E5…E85, bio diesel ethanol, methanol, kerosene, fatty acid methyl ester, oils
Equipment : Strainer- Gas elmination device : EC EC 32(50 to 450µ fitering (270 to 40 mesh) depending on the liquids Gas release controlled by float and differential valve)
PD meter : ZC 17-80
Temperature measurement : 4-wire Pt100 (option for electronic calcuator version)
Multi-funcion valve : Small and large flow, authorisation, flow limination
Flow register : Mechanical register model VR with pre set, printer, pulser (option) or Equalis flow computer with display, secure arching of transactions.
Operating conditions :
Pressure : 10 bar max
Viscositas : 20 cSt max- Constant us about higher viscosities
Liquid temperature : -10 to +80°C
Ambient temperature : Standard : -25 to +55°C; Option -40 to +55°C
Metrological performances
Accuracy : ≤0.15%-option ≤0.1%-for measurement range of 10 : 1
Repeatability : ≤0.02 %
Temperature accuracy : ≤0.5°C