Description
- For general information concerning the operation of a hidrobloc control valve, please consult our general manual (series K)
- Extensive range including two different designs :
– XG Design :
– Large flow capacity
– Low head loss
– Watertight at zero flow rate
– XGS design :
– Particularly suitable for pressure reduction
– Better cavitation resistance
– Watertight at zero fow rate
Construction
- Self-lubricated double guided mobile unit
- Ductile iron body and bonnet
- Stainless steel seat for standard version until DN 400 XG design and DIN 600 XGS design
- Powder epoxy coating
- Stainless steel pilot circuit tube and fittings
- Pilot circuit strainer with screen in stainless steel
- Individually packed
Easy operation and maintenance
- Visual position indicator with manual drain
- Including isolating valve(s) for pressure gauges
- Equipped with opening speed controller “RO” (DN50 to 300 XG design, and DN150 to 400 XGS design only)
- Chamber isolating valve independent from the adjustment of the speed controller
- Maintenance without disassembly from the pipeline
- Drain plug (stainless steel)
Product according to standard EN 1074-5
Technical Data
- Range DN 300 for XG design and XGS design
- PN 25
- Maximum temperature +1°C to +65°C
- Seating class A according to standard ISO 5208-2
- Face-to-face dimensions according to standard EN 558-1 series 1 (except DN 1000) and ISO 5752 series 1 (except DN1000)
- Flange drilling according to standard EN 1092-2 and ISO 7005-2; ISO PN 10, 16 or 25 for DN50 to 1000 (other drillings please consult us)
- Fluid drinking water or 2 mm filtered untreated water
- Working pressure 25 bar
- Vertical and horizontal installation
- The valve body of PN 16 and PN 25 are the same the difference are on flange drilling and pilot circuit
Specifications
- XGS design :
– B : 524 mm
– C : 631 mm
– D : 242 mm
– Weight : 195 kg - XGS design :
– B : 606 mm
– C : 657 mm
– D : 242 mm
– Weight : 219.8 kg