Flow Meter SATAM ZCE 6-80

Metering system for truck and railcar loading
Model : ZCE 6-80

ZCE 6 horizontal metering unit is designed for truck and train tankers loading stations in a top or buttom configuration

ZCE 6 space-saving configuration enables easy installation in smaller facilities and in compact pipeline network

Sector of application

  • Tanker truck and railcars loading applications
  • Preparation of fuels by means if online on batch blending
  • Measurement of white product and bio-fuels

High reliability measuring system

Ready-made technology ZCE 6 horizontal measuring systems are completely assembled, wired and tested in the production facility in order to ensure a maximum reliability

Measurement stability and accuracy Measurement accuracy guaranteed over a period of many years without any deviation in the calibration curve

Modular design
extensive line of accessories to create customized meassurement pplications

Key points
Low installation costs
Complete and ready-to-install measuring unit including strainer, air eliminator, PD meter, valve and register

Low maintenance costs
Simple and robust constructions with minimal moving parts Interchangeable mechanical components

Space-saving installation
Compact metering unit for installation in smaller areas and in vertical pipeline networks

A safe and easy-to-use-technology
Automatic gas elimination system to start loading operation with empty pipe. Filtering system with automatic slogging detection (option0

Communication
Direct communication with supervisory with the electronic register version

Technical data-Horizontal metering system
Measuring system : ZCE 6-80
Maximum flow rate m3.h-L/mn-USGPM : 80-1333-360
Application : Tanker truck and rail car loading application, product transfert
Measured parameters : Actual volume, temperature-corrected volume, mess, flow rate, temperature (only for electronic register version, option for mechanical register version)
Measured liquids : Petrol, premium fuels, diesel, E5…E85, bio diesel, ethanol, methanol, kerosene, fatty acid methyl ester, oil
Equipment
Temperature measurement : 4 – wire Pt100 (option for electronic calculator version)
Multi-function valve : Small and large flow, authorisation flow limitation
Flow register : Mechanical register model VR with pre set, printer, pulser ( option) or Equalis flow computer with display, secure archiving of transactions

Operating conditions :
Pressure : 10 bar max
viscosity : 20 cSt max-Contact us about higher viscosities
Liquid temperature : -10 to +80°C
Ambient temperature : Stabdard : -25 to 55°C, option -40 to 55°C

Metroligical performances
Accuracy : ≤0.15%-option ≤0.1%-for measurement range of 10:1
Repeatability : ≤0.02%
Temperature accuracy :≤0.5°C