Description
- For general information concerning the operation of a hidrobloc caontrol valve, please consult our general manual (series K)
- Extensive range including two different design :
– XG design :
– Large low capacity
– Low head loss
– Watertight at zero flow rate
– XGS design
– Particularly suitable for pressure redusction
– Better cavitation resistance
– Watertight at zero flow rate
Construction
- Self-lubricated double guided mobile unit
- Ductile iron body and bonnet
- Stainless steel seat for standard version until DN 400 XG design and DN 600 XGS design
- Powder epoxy coating
- Stainless steel bolting
- Stainless steel pilot circuit tube and fittings
- Pilot circuit strainer with screen in stainless steel
- individually packed
Easy operation and maintenance
- Visual position indicator with manual drain
- Including isolating valve (s) for pressure gauges
- Equipped with opening speed controller “RO” (DN 50 to 300 XG design, and DN 150 to 400 XGS design only)
- Chamber isolating valve indevendent from the adjustment of the speed controller
- Maintenance without disassembly from the pipeline
- Easy dismantling from the top
- Drain plug (stainless steel)
Product according to standard EN 1074-5
Technical Data
- Range for XG design
- PN 25
- Maximum temperature +1°C to +65°C
- Seating: Class A according to standard ISO 5208-2
- Face to face dimensions according to standard EN 558-1 series 1 (except DN 1000) and ISO 5752 series 1 (except DN1000)
- Flange drilling according to standard EN 1092-1 and ISO 7005-2; ISO PN 10, 16 or 25 for DN50 to 1000 (other drillings, please consult us)
- Fluid: drinking water or 2 mm filtered untreated water
- Working Pressure 25 bar
- Vertical and horizontal installation
- The valve bodu of PN 16 and PN 25 the same, the difference are on fange drillings and pilot circuit
Specifications
- XG design :
– B : 307 mm
– C : 396 mm
– D : 137 mm
– Weight : 43.2 kg